9.3
Item List Including Maintenance and Spare Parts
Pos.
Denomination
1
Gate valve
Primary circuit
2
Actuating drive
3
Bourdon tube gauge
4
Bourdon tube gauge
5
Machine thermometer
6
Plate heat exchanger
7
Plate heat exchanger
8
Safety valve
9
Pressure control device (min)
10
Extension tank
11
Dirt trap
12
Block pump
13
Non-return valve
14
Screwed-in sensor
CoolTrans
Type / Make
Samson 322k
DN 50 (10/4"AG) PN 25 kvs 25 150°C RG
Samson 5825-25 STR II IP 54
24 VAC 0-10V/4-20, actuating time: 70s lift: 12mm
Manotherm 0 ...16 bar
DM:100mm ½", connection from below 140°C GK 1,0
Manotherm 0..6 bar
DM:100mm ½", connection from below 140°C GK 1,0
Sika -30 ... 50°C
Typ 174 B 110x30 straight L=63mm ½" MS
WTT WP 7-50 M DN 50
WTT WP 7-150 M DN 50
Götze 851 BF
½" x 1" IG 2,5 bar Rg / EPDM, distinguishing letter F
Sauter DSB 138 F001
DN15 (1/2" AG) PN 12 70°C 0..1.6bar TÜV
Reflex F24
DN 20 (3/4" AG) PN 3, admission pressure 1.5 bar
Barberi DN 50 (2" IG)
PN 16 110°C Ms
Wilo BAC 40/128-1,5/2-s
DN 40 (6/4") x DN 50 (2") PN 6 400VAC -15..60°C
Rittag SR 70.16
DN 50 PN 16 120°C, brass, intermediate flange
Ni1000TK5000, SFK 01
-50 ... +160°C, replaceable, 150 x 8 x 1 mm
01.998.362.0 / Ausgabe f
(FL) PN 30, without consoles
(FL) PN 30, without consoles