CoolTrans
Manual / Bedienungsanleitung
Selecting a language
Main menu > settings > device >
Operational line
Sprache
Language
.
.
Setting the flow temperature
Main menu > settings > controller1 > setpoints
Operational line
upp prcom setp
upper comf setp
low comf setp
low prcom setp
First set "upp prcom setp" and "low prcom setp" for the desired cooling water flow temperature, then
set "upper comf setp" and "low comf setp" for the desired temperature. All four values need to equal
each other.
Polling service life
The length of service life of the pumps can be polled from the control.
Main menu > settings > data collection > operating hours > operating hours 1 ... 2
Operational line
Operating hours*
Operating hours since
maintenance
Reset**
* Displaying accumulated hours of operation, counting up to 99,999 hours, then beginning at 0
again
** This data item resets the item "Operating hours since maintenance" to 0 hours
CoolTrans
Range
de
en
.
.
Range
Range
Display 0 ... 99 999 h
Display 0 ... 99 999 h
No, Yes
01.998.362.0 / Ausgabe f
Default setting
Deutsch
English
.
.
Default setting
12°C
12°C
12°C
12°C
Default setting
No
page / Seite21/80