Herunterladen Diese Seite drucken

IFM Electronic Efector300 SI0509 Bedienungsanleitung Seite 33

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

I I Activate / deactivate the function for remote adjustment
If the function is active, the unit can be adjusted by applying voltage
to pin 2.
Unit supplied: function active.
Function
LO
active
Function
LO
not active
*The LEDs flash if voltage is applied to pin 2.
M
S
1
3 x
M
S
>5 s
2
M
S
3
If the function for remote adjustment is active and the operating
voltage is applied to pin 2 for more than 20 s, the unit is locked (the but-
tons are inactive as long as the operating voltage is applied to pin 2).
Use 4-wire connection cables without a link between pins 2 and 4.
With 3-wire sockets with a link between pin 2 and pin 4 switching of
the output stage triggers the remote adjustment!
34
HI
HI
LO
LO
LO
LO
The 3 LEDs on the right and left are lit in
green.*
The 4 LEDs in the middle are lit in red.*
Press the Mode/Enter button three
HI
times.
The current setting is indicated.
HI
Press the Learn/Set button and
keep it pressed,
after 5 s the function changes.
HI
(Each time the Learn/Set button
is pressed the function changes
again).
Press the Mode/Enter button
briefly (= acknowledgement).
HI
The indication goes off briefly,
the unit then passes into the
operating mode.

Werbung

loading