Programming
I I Setting of the detection range
HI-Teach
• Allow the medium to flow through the system at the required maxi-
mum flow rate.
• Press the Learn/Set button for for > 5 . . . < 1 0 s (= adjustment to
maximum flow / upper limit of the detection range).
Optional: LO-Teach
The HI-Teach is sufficient for the majority of waterbased applica-
tions. Optional: adjustment to minimum flow.
• Allow the medium to flow through the system at the required mini-
mum flow rate or bring flow to a standstill.
• Press the Learn/Set button for >10...<15 s (= adjustment to mini-
mum flow or flow standstill / lower limit of the detection range).
I I Remote adjustment via programming wire
Apply the operating voltage (+U
I I Setting of the switch point
• Press the Mode/Enter button briefly.
• Press the Learn/Set button for 5 s,
• keep the Learn/Set button pressed or press the button several times
until the requested switch point is set.
• Press the Mode/Enter button briefly.
I I Monitoring excess flow
• Press the Mode/Enter button twice.
• Press the Learn/Set button for 5 s, release the button when LED
flashes.
• Press the Learn/Set button several times to shift the LED for the
maximum display value.
• Press the Mode/Enter button briefly.
) to pin 2 for the respective time.