Siemens 3WX3641 JR Serie Betriebsanleitung Seite 25

Überstromauslöser für leistungsschalter, ausführung r, s/t

Werbung

Parameterizing values are examples
value U
value f
value P
protec.
misc.
misc.
misc.
misc.
I_ab
I_an
ZSS
misc. I_ab
misc. I_an
misc. ZSS
= 400 A
=on/off
= 800 A
misc. I_an
misc. ZSS
misc. I_ab
#1000A
#500A
#on/off
misc. I_an
misc. ZSS
misc. I_ab
?1000A
?500A
?on/off
misc. I_an
misc. ZSS
misc. I_ab
=1000A
=500A
=on/off
misc.
misc.
misc.
U<
U>
*
*
*
Menu misc.
In this menu option, setting of additional protective parameters is
carried out.
misc. ZSS:
enabling and disabling of the short-time grading
control
2
misc. I
t
:
enabling and disabling of the I
d
teristic of the short-time grading control
misc. I
2
t
:
enabling and disabling of the I
d
ter of the earth-fault protection
misc. mem:
enabling and disabling of the thermal memory
misc. phasl:
enabling and disabling of the phase-failure sensi-
tivity
misc. syml:
here, the operate value for permissible current
unbalance of the phases is determined. The adjust-
able values are 50 % or "off". If the menu option
relay opt is enabled, on occurrence of the
parameterized unbalance, the output "optional sig-
nal" is set and the circuit-breaker is tripped after
elapse of the delay time set under relay tx.
misc. symU:
not available
misc. EF:
not available
misc. f<:
not available
misc. f>:
not available
misc. U<:
not available
misc. U>:
not available
misc. I _off: here is set the operate value for load shedding. The
adjustable values are in the range of (20 % to 150 %) x l r or "off".
Caution
The signal is only active after elapse of the delay time
set under menu option relay tx.
If the signal "lead time overload trip pending" is to be
used, this parameter must be set to off.
misc. I _on: here is set the operate value for load shedding. The
adjustable values are in the range of (50 % to 150 %) x I r or "off".
The signal is only active after elapse of the delay time
set under menu option relay tx.
value I
menu
relay
status
misc.
misc.
I2td
I2tg
misc. I2td
misc. mem
misc. mem
misc. I2tg
=on/off
=on/off
=on/off
=on/off
misc. I2td
misc. I2tg
misc. mem
misc. mem
#on/off
#on/off
#on/off
#on/off
misc. I2td
misc. I2tg
misc. mem
misc. mem
?on/off
?on/off
?on/off
?on/off
misc. I2td
misc. I2tg
misc. mem
misc. mem
=on/off
=on/off
=on/off
=on/off
misc.
misc.
EF
f<
f>
*
*
2
t = constant charac-
2
t = constant charac-
protec.
misc.
misc.
misc.
mem
phasI
mem
mem
symI
misc. mem
misc. mem
misc. mem
misc. mem
=on/off
=on/off
=on/off
=off
misc. mem
misc. mem
misc. mem
misc. mem
#on/off
#on/off
#on/off
#50%
misc. mem
misc. mem
misc. mem
misc. mem
?on/off
?on/off
?on/off
?50%
misc. mem
misc. mem
misc. mem
misc. mem
=on/off
=on/off
=on/off
=50%
misc.
symU
*) not available
protec.
misc.
status
Parameterizing values are examples
Menu relay
relay g:
on - exceeding the operate value of the earth-fault protection
leads to trip
off - exceeding the operate value of the earth-fault protection
activates the earth-fault LED. Indication can only be reset
after the operate value has been undershot
This is possible only on overcurrent releases S and T.
relay temp:
on - exceeding the temperature limit in the release enclosure
activates the optional signal (the optional signal must be
enabled by the relay opt. menu option)
off - exceeding the temperature limit in the release enclosure
activates not signal
relay opt.
on - the optional signal is activated if at least one of the enabled
causes is present (Addition syml or relay temp)
off - optional signal is disabled
relay tx:
Delay time for menu options: Addition I _off, Addition I _on.
value f
value U
value P
misc.
status
status
status
status
status
In
Test
D-Nr.
L-Nr.
status In
status Test
status D-Nr
status L-Nr
= 1600 A
=System OK
= 23456
Measure values are example
Menu status
In this menu option, status information is
displayed.
status D No., status L No.: not available
status bus: higher-level communication bus
system (if present)
status l n :
circuit-breaker rated current
The rated current value may only be changed
when the release is removed (disconnected)
from the circuit-breaker. The entered value
must be identical to the value of the rated
current on the rating plate of the circuit breaker.
Incorrect entry will cause false or delayed
tripping. After I
all protective parameters (I
n
I
, I
,...) should be checked.
d
i
status Test: result of the internal release test
value P
value f
relay
relay
relay
relay
tx
g
temp
relay tx
relay g
relay temp
= 10 s
= on/off
= on/off
relay tx
relay g
relay temp
# 15 s
# on/off
# on/off
relay tx
relay g
relay temp
? 15 s
? on/off
? on/off
relay tx
relay g
relay temp
= 15 s
= on/off
= on/off
value I
menu
relay
status
Bus
status Bus
= 3
= RS485
,
n
value U
value I
Menu
relay
opt.
relay opt.
= on/off
relay opt.
#= on/off
relay opt.
? on/off
relay opt.
= on/off
25