Siemens 3WX3641 JR Serie Betriebsanleitung Seite 24

Überstromauslöser für leistungsschalter, ausführung r, s/t

Werbung

6 Menu
Menu structure
status
relay
menu
value I
value I
value I
g
L3
N
value I L3
value I N
value I g
= 1405 A
= 463 A
= 77 A
Measure values are example
Menu value I
In this menu option, all measured currents are displayed. If the
value is less than 18% of I n , display of the value is suppressed. The
characters o and ¤ will then appear alternately on the display.
value I aktL :
current in the highest-loaded phase
value I maxL :
maximum current which has flowed in the
last 15 minutes
value I minL :
minimum current which has flowed in the last
15 minutes
value I L1, L2, L3:
operating current in phases L1, L2, L3
value I N :
current in neutral conductor
value I g :
earth-fault current
value IPhSeq:
not available
menu value U
not available
menu value f
not available
menuvalue P
not available
* parameter values "g/N"
Version No. g/N
Neutral conductor
Earth fault protection
only model S/T
Protection is disabled
N
Neutral conductor protection with fourth transformer
Separate earth-fault iron-cored transformer
Earth-fault protection by summation
24
misc.
protec
value U
value I
value I
value I
value I
value I
PhSeq
aktL
maxL
minL
valueIPhSeq
value ImaxL
value IaktL
value I minL
= < --
= 1467 A
= 1580 A
= 870 A
0
1
N
value P
value f
value I
value I
L1
L2
value I L1
value I L2
= 1580 A
= 870 A
value U
value f
value P
protec.
protec.
protec.
protec.
Ig
tg
g/N
Inext
*
protec. Ig
protec. tg
protec.g/N
protec.Inext
= 300 A
= 400 ms
= 2
= 1000 A
protec. Ig
protec. tg
protec.g/N
protec.Inext
# 400 A
# 500 ms
# 1
# 1200 A
protec. Ig
protec. tg
protec.g/N
protec.Inext
? 400 A
? 500 ms
? 1
? 1200 A
protec. Ig
protec. tg
protec.g/N
protec.Inext
= 400 A
= 500 ms
= 1
= 1200 A
Parameterizing values are examples
Menu protec.
In this menu option, setting of the basic protection parameters is
carried out.
protec. I N :
protec. I r :
protec. T c :
protec. I l :
protec. I d :
protec. t d :
protec. I g :
protec. t g :
protec. g/N:
protec. Inext:
value I
menu
misc.
protec.
protec.
protec.
protec.
IN
Ir
Tc
protec. IN
protec. Ir
protec. Tc
protec. Ii
= 500 A
= 1100 A
= 6 s
= 22000 A
protec. IN
protec. Ir
protec. Tc
protec. Ii
# 600 A
# 1200 A
# 10 s
# 20000 A
protec. IN
protec. Ir
protec. Tc
protec. Ii
? 600 A
? 1200 A
? 10 s
? 20000 A
protec. IN
protec. Ir
protec. Tc
protec. Ii
= 600 A
= 1200 A
= 10 s
= 20000 A
overload protection for the neutral conductor,
20 to 100 % of I n
current setting for overload protection,
40 to 100 % of I n
time-lag class for overload protection, 2 to 30 s
or "off" (overload protection disabled)
operate value for instantaneous short-circuit
trip, 1,5 x I n bis 12 x I n
operate value for short-time-delay short-circuit
trip, 1, 25 x I n bis 12 x I n
delay for short-time-delay short-circuit trip,
20 to 400 ms. If t
is set to values above 500 ms,
d
I d is automatically limited to max. 15 kA
operate value for earth-fault trip,0, 2 of I n to 0, 6
of I n (max. 1200 A) (Menu: relay, Alarm or
setting trip)
delay for earth-fault trip, 100 to 500 ms
specification of type of earth-fault and neutral
conductor protection
rated current of external earth-fault iron-cored
transformer, 200 to 3200 A
relay
status
protec.
protec.
protec.
Id
td
Ii
protec. Id
protec. td
=10000 A
= 200 ms
protec. Id
protec. td
# 8000 A
# 150 ms
protec. Id
protec. td
? 8000 A
? 150 ms
protec. Id
protec. td
= 8000 A
= 150 ms