Never connect more than one SYMPL Node in factory state
i
to a network. The identical IP addresses will conflict and
disturb proper communication.
The Ethernet port of the SYMPL Node is not designed for
i
inter-building connections with power and lighting transients.
Use only intra-building networks to connect the SYMPL
Nodes and Cores.
4.4
DMX connection
The SYMPL dmx Node can control two DMX512 universes with its two
DMX ports. Connect DMX devices to the SYMPL Node using 3-pin terminal
plugs at the DMX interface of the SYMPL Node.
The appropriate pin assignment is defined as follows:
From left to right: GND, DMX-, DMX+
It is recommended to use twisted pair cabling.
4.5
Power supply
The e:cue SYMPL dmx Node can be powered by an external power supply
or via Power-over-Ethernet.
PoE:
For PoE, simply connect an Ethernet connection from a power sourcing
device.
External power supply:
Connect the SYMPL dmx Node to a certified NEC Class 2 24 V DC power
supply unit. Present power supply equates to the status "On" or running of
the SYMPL Node.
Installation
15