Abus Terxon MX Installationsanleitung Seite 173

Vorschau ausblenden Andere Handbücher für Terxon MX:
Inhaltsverzeichnis

Werbung

Unset 4
This output is activated for a definable
time period (command 170) if the alarm
33
centre is deactivated completely (A) or
internally (B), (C) or (D) (command
171).
Fire
This output is activated if a fire alarm is
triggered. The output remains active
34
until the alarm is deactivated.
PA
This output is activated if a fire alarm is
triggered. The output remains active
35
until the alarm is deactivated.
4. Confirm your input. On the control unit, enter:
.
5. The control unit acknowledges your input with a
double "beep" tone and shows Installer Mode.
082 Relay output OP2
To change the behaviour of relay output OP2 on the alarm
centre PCB:
1. On the control unit, enter:
2. The LCD display shows: 082: Strobe
3. Via the keypad, select from the items described
above and enter the function accordingly:
083 Transistor output OP3
To change the behaviour of transistor output OP3 on the
alarm centre PCB:
1. On the control unit, enter:
2. The LCD display shows: 083: Set Latch
3. Via the keypad, select from the items described
above and enter the function accordingly:
085 Burglary output
To change the behaviour of the transistor output on
burglar alarms:
082
083
69
1. On the control unit, enter:
2. The LCD display shows: 085: Burg=Latched
3. Via the keypad, select from the following items
and press:
Burg=Latched
The output remains activated until the
00
user or programmer resets the alarm
centre.
Burg=Rearm
The output is reset following expiry of
01
the defined siren duration. It can be
reactivated in the event of a new alarm.
4. Confirm your input. On the control unit, enter:
.
5. The control unit acknowledges your input with a
double "beep" tone and shows Installer Mode.
086 Additional entry delay
To change the behaviour of the entry delay time:
1. On the control unit, enter:
2. The LCD display shows: 086:Dual Ply OFF
3. Via the keypad, select from the following items
and press:
Dual Ply OFF
0
An alarm is triggered following expiry of
the entry delay time.
Dual Ply ON
An internal alarm is triggered following
1
expiry of the delay time. The user has
another 30 seconds to enter the user
code and deactivate the alarm centre.
4. Confirm your input. On the control unit, enter:
.
5. The control unit acknowledges your input with a
double "beep" tone and shows Installer Mode.
085
086
UK