Mounting and installation
EN
EN
EN
EN
EN
EN
EN
7.3.2 Conductor Connection
• Select suitable conductors that do not exceed the permitted heating temperature
EN
within the enclosure.
EN
• Ensure that conductors have the specified cross sections.
EN
• Guide the conductor insulation so that it reaches the terminals.
EN
• Do not damage the conductor when stripping the insulation (e.g. by denting it).
• Attach the core end sleeves properly.
EN
• If the system is equipped with all possible clamps and live conductors, and and the
EN
maximum current load has been reached, ensure that the length of a conductor from
EN
the screw connection to the terminal point does not exceed the diagonal planes of the
enclosure.
EN
EN
Connecting conductors to built-in elements with screw terminals:
EN
Where built-in elements have screw terminals, 1 or 2 cables may be connected to a single
connection terminal. In case of solid conductors, both conductors must have the same
EN
cross section and must be made of the same material.
EN
The conductors can be connected without previous measures.
EN
Connecting conductors to built-in elements with screwless terminals
EN
(contact elements shown as example):
EN
EN
EN
EN
Intrinsically safe circuits
14
Control and monitoring devices
ConSig 8040 series
Explosion hazard due to open drilled holes and unused cable entries!
Non-compliance results in severe or fatal injuries.
• Tightly seal open drilled holes using appropriately certified stopping
plugs (e.g. Type 8290) and unused cable entries using certified plugs
(e.g. Type 8161).
DANGER