Network Status LED
Status
Lights up green
Flashes green (once)
Flashes green (per-
manently)
Lights up red
Flashes red (once)
Flashes red (twice)
Flashes red (three
times)
Module Status LED
Status
Off
Lights up green
Flashes green (once)
Lights up red
Lights up green and
red alternately
Connection/activity LED (5+6)
Status
Off
Lights up green
Flickers green
Data Transfer
Transfer technology:
Properties
Ethernet
Medium
When selecting the cable, plug, and terminating resistors, the Profinet assem-
bly guideline for the planning and installation of Profinet systems must be ob-
served.
The EMC tests were carried out by the manufacturer with the cable IEC-C5D-
D4UGG0150A20A20-E.
The EMC tests were carried out by the manufacturer with a bus cycle time of
32 ms.
Transmission speed:
100 Mbit/s, full duplex mode
30
Meaning
Online (RUN); connection with IO Controller establis-
hed,
IO Controller in operation
Online (STOP); connection with IO Controller establis-
hed, IO Controller not in operation, IO data defective,
IRT synchronization not ready
In use by engineering tools in order to identify network
nodes
The module has identified a serious internal fault
Station name not set
IP address not set
Configuration error; expected identification does not
match the actual identification
Meaning
No supply voltage or
module in the setup or initialization mode
Normal operation
Diagnosis process running
Emergency situation, serious fault, etc.
Firmware update. Do not disconnect the module from
the power supply during the update—this could result
in damage to the module.
Meaning
No connection, no activity
Connection established, no activity
Connection established, activity present