12.3. FAN CONTROL WHEN SPEED IS SET USING CONTROLLER AND/
OR COMPUTER VIA MODBUS
Using this remote controller and CO
This controller allows controlling both device and 0..10 VDC fan. In service menu, select desired
speed control method (F.01). If control based on preset speeds is selected, then select them in menu
items F.03, F.04, F.05, F.06.
NOTE: The air quality converters and remote controller (when fan is controlled) must be powered
from a separate power source. It is not supplied with the remote.
12.4. PRESSURE CONTROL WHEN SELECTED USING CONTROLLER
AND/OR COMPUTER VIA MODBUS
Desired pressure can be maintained by connecting 0..10 VDC fan and 0..10 VDC pressure convert-
er directly to the controller. Control and pressure sensor parameters can be changed in controller.
When controller is used as Modbus slave device (air handling unit is not controlled by this principle),
it allows controlling all parameters and monitoring of pressure sensor readings.
For pressure based control, select the following parameters in the service menu:
F.01 - 2
F.14 - 1
F.15 and F.16 - based on pressure converter parameters
F.11, F.12 and F.13 - (PID control ratios). If pressure is maintained incorrectly, these parameters
can be adjusted.
F.0 - F.10 - seting of fixed speeds (supports different pressure level in Pa)
F.43 -1 - 0..10VDC output activated.
12
| EN
RC
MODBUS
RC
- controller (master); FAN - fan
transmitter it is possible to reduce inside carbon dioxide level.
2
MODBUS
RC
0...10 VDC
MODBUS
RC
0...10 VDC
MODBUS
0...10 VDC
RC
- controller (master); PS
RC
0...10 VDC
AHU
AHU
AHU
MODBUS
AHU
0...10 VDC
RC
0...10 VDC
RC
MODBUS
0...10 VDC
AHU
FAN
0...10 VDC
RC
MODBUS
PS
0...10 VDC
RC
0...10 VDC
BMS
PS
-
pressure sensor; FAN - fan
FAN
MODBUS
AHU
PS
RC
BMS
AHU
RC
FAN
FAN
PS
FAN
AHU
FAN
RC
RC
STOUCH v2019.1

Werbung

loading