Helios KWL Yoga Style 400 Montage- Und Betriebsvorschrift Seite 54

Dezentrales lüftungsgerät

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Installation and Operating Instructions
EN
Service menu | 02 – Hw setting (Hardware)
50 -
01 -
04 -
05 -
Select contact
logic for switching
using motion sensor
or fire contact
– Operating signal potential-free contact (15-16):
The logic of the connected potential-free contact can be set as follows:
– N. closed (normally closed)
– N. open (normally open)
– Hot water heater battery frost protection:
Behaviour of extract air fan for hot water heater battery frost protection
Selection: Extract air fan on/off when hot water frost protection triggered.
Service menu | 04 – Fan calibration
01 -
02 -
05 -
08 -
Fan calibration
Fan calibration is not required for KWL Yoga ventilation units. However, the
maximum flow rate can be limited in this menu.
Decentralised ventilation unit – KWL
Factory reset
Mode
Hw Setting
Fan calibration
Filter calibration
Hw setting
Digital input (15-16)
fire input
Digital output RUN (7-8)
Select RUN
N�Close
contact logic
Mode
Hw Setting
Fan calibration
Filter calibration
AQS Sensor
Calibration
Start calibration
®
Yoga Style/KWL
Service menu | 05 – Filter calibration
02 -
Hw Setting
04 -
Fan calibration
Filter calibration
08 -
AQS Sensor
09 -
Temperature sensor
The calibration must be carried out for the initial commissioning and after a
filter type change.
Service menu | 08 – AQS Sensor (air quality sensor)
04 -
Fan calibration
05 -
Filter calibration
AQS Sensor
09 -
Temperature sensor
10 -
Supply Duct Limits
It is recommended to select 2000 ppm when using a Helios CO2 room
AQS Sensor
Select air
quality
sensor
AQS Limits
Maximum CO
2
limit
The function is available when an Air Quality Sensor (CO
installed. This is only available with the optional AQS duct sensor (upon request). If the
air quality is better than the lower sensor limit value, the unit will be deactivated. After 10
minutes, the unit will be operated for one minute at minimum speed to carry out another
air quality test (respiration).
If the air quality is still lower than the lower sensor limit value, the unit will deactivate
again. After 10 minutes, the unit will be operated for one minute at minimum speed to
carry out another air quality test (respiration).
If the air quality is higher than the lower sensor limit value, the unit will continue to run
and slowly increase the speed to the maximum value within 5 minutes. The unit will
continue operating at maximum speed for 2 minutes. During this time, the air quality
sensor measurement value will be ignored. The unit will then return to automatic sensor-
controlled operation.
21
®
Yoga Style ET
Max. flow
None
Set the limit va-
AQS Limits
lues for air quality
sensors
Respir.
Select air quality test
Minimum CO
sensor, humidity sensor) is
2
sensor.
limit
2