– The ventilation machinery and outlets are
operating adequately and are not obstructed;
– If an indirect refrigerating circuit is being
used, the secondary circuit shall be checked
for the presence of refrigerant;
– Marking to the equipment continues to be
visible and legible. Markings and signs that are
illegible shall be corrected;
– Refrigeration pipe or components are
installed in a position where they are unlikely to
be exposed to any substance which may
corrode refrigerant containing components,
unless the components are constructed of
materials which are inherently resistant to
being corroded or are suitably protected
against being so corroded.
9) Checks to electrical devices
Repair and maintenance to electrical
components shall include initial safety checks
and component inspection procedures. If a
fault exists that could compromise safety, then
no electrical supply shall be connected to the
circuit until it is satisfactorily dealt with. If the
fault cannot be corrected immediately but it is
necessary to continue operation, an adequate
temporary solution shall be used. This shall be
reported to the owner of the equipment so all
parties are advised.
Initial safety checks shall include:
• That capacitors are discharged: this shall be
-66-