GEZE TS 5000 R-ISM BG Montageanleitung Seite 20

Gleitschiene für bandgegenseite mit integrierter schließfolgeregelung, rauchschalter und elektrischer feststellung
Vorschau ausblenden Andere Handbücher für TS 5000 R-ISM BG:
Inhaltsverzeichnis
Verfügbare Sprachen

Verfügbare Sprachen

Mounting and securing
Stop rod may not pass under driver.
Pull out stop rod (3.).
X
Distance between edge block and stop is approx. 30 mm
Close moving leaf (4.).
X
Stop rod for function safeguard of the integrated closing sequence control is in position.
Open moving leaf (5.).
X
Tighten screws of stop rod (6.)
X
6. 1 2 Mounting cover panels
CAUTION!
Do not pinch cable.
X
= B - 1189 mm
C
C
= D - 10 mm
35
GF
Important: The smoke detector opening from the middle cover panel must be positioned over the smoke detector.
If necessary, dimension „D" can be measured between the leaf cover panels.
Remove break-off section on fixed leaf for trigger lever (1.).
X
Clip on moving-leaf cover panel and fixed-leaf cover panel (2.).
X
Shorten adjustable-size middle cover panel „A" to size „C" (Fig. 6.12.1).
X
Clip on middle cover panel (3.).
X
Clip on protective cap (4.).
X
Insert inspection caps between cover panels (5.).
X
CAUTION!
Attach protective cap in such a way that the smoke switch opening is concealed in the cover to protect
X
the interior of the system from contamination.
Protective cap must be removed during commissioning of the hold-open device.
GB 9
4.
5.
2.
(5)
5.
3.
B
D
C
(5)
A
TS 5000 R-ISM BG
1.
2.
35
SF
Fig. 6.12.1