NOTICE
grounding, or asymmetric-grounding network, put the EMC Filter screw or screws in the OFF position to disable
the built-in EMC filter. If you do not disable the built-in EMC filter, it will cause damage to the drive.
If you lose an EMC filter switch screw, use
install the new screw with the correct tightening torque.
NOTICE
can cause damage to the drive.
Model
2018
4009
2025 - 2075
4015 - 4045
Safe Disable Input
Overview
This section gives precautions to support the Safe Disable input. Contact Yaskawa for more
information.
The safety function complies with the standards shown in
Function
EN 62061 (SILCL3)
Functional
Safety
EN 61800-5-2 (SIL3)
ISO/EN ISO 13849-1:2015 (Cat.3, PL e)
Machine Safety
EN 61800-3
EMC
EN 61800-5-1
LVD
Note:
SIL = Safety Integrity Level.
YASKAWA TOMPYEULA5001C LA500 Installation and Operation Instructions
Figure 1.11 Symmetric Grounding
Damage to Equipment. When you use the drive with a non-grounding, high-resistance
Only use the screws specified in this manual. If you use screws that are not approved, it
Table 1.9 Screw Sizes and Tightening Torques
Table 1.10 Applied Unified Standards
Table 1.9
to find the correct replacement screw and
Screw Size
M3 × 20
M4 × 20
Table
Unified Standards
Tightening Torque
N∙m (in∙lb)
0.5 - 0.6
(4.4 - 5.3)
1.2 - 1.5
(10.6 - 13.3)
1.10.