Model
Terminal
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
2047
-, +1, +2
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
2060
-, +1, +2
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
2075
-, +1, +2
B1, B2
*1
Remove insulation from the ends of wires to expose the length of wire shown.
*2
If you turn on the internal EMC filter, the leakage current of the drive will be more than 3.5 mA. Use the closed-
loop crimp terminals to connect a protective ground wire that has a minimum cross-sectional area of 10 mm
(copper wire).
YASKAWA TOMPYEULA5001C LA500 Installation and Operation Instructions
Recomm.
Applicable
Gauge
Gauge
2
2
mm
mm
16
4 - 25
16
4 - 25
25
6 - 35
10
4 - 16
10
10 - 25
25
6 - 35
16
6 - 25
35
10 - 50
10
4 - 16
16
10 - 25
35
10 - 50
25
10 - 35
50
16 - 70
16
4 - 16
16
10 - 25
Wire
Terminal Screw
Stripping
Length
*1
Size
Shape
mm
18
M5
18
M5
18
M5
10
M4
-
M6
20
M6
20
M6
20
M6
10
M4
-
M6
20
M6
20
M6
20
M6
10
M4
-
M6
9 Attachment
Tightening
Torque
N∙m (in∙lb)
2.3 - 2.5
(19.8 - 22)
2.3 - 2.5
(19.8 - 22)
• ≤ 25 mm
2
2.3 - 2.5
(19.8 - 22)
• 35 mm
2
4.1 - 4.5
(36 - 40)
1.5 - 1.7
(13.5 - 15)
5.4 - 6.0
(47.8 - 53.1)
5 - 5.5
(45 - 49)
5 - 5.5
(45 - 49)
5 - 5.5
(45 - 49)
1.5 - 1.7
(13.5 - 15)
5.4 - 6.0
(47.8 - 53.1)
5 - 5.5
(45 - 49)
5 - 5.5
(45 - 49)
5 - 5.5
(45 - 49)
1.5 - 1.7
(13.5 - 15)
5.4 - 6.0
(47.8 - 53.1)
2
267