5. Technical data LSP 4L
Nominal voltage range: 12 ... 690 V AC / DC
Nominal frequency range: 0 ... 500 Hz
Measurment range:
Input resistance:
Current peak value I
:
s
On-time:
Display :
Power supply:
Overvoltage category:
Surge voltage strength:
Test voltage:
Operating temperatures: -15 ... + 45°C
Casing:
Protection category:
Connecting line:
Standards:
EMV requirements:
Dimensions:
Weigth:
DC: 12 ... 690 V (± 3 % + 4 D)
AC: 12 ... 690 V (± 3 % + 4 D)
approx 167 kΩ AC / DC
at 690 V
approx 200 kΩ AC / DC
at 50 V
4,2 mA at 690 V AC / DC
TR
30 s at 690 V
on
RT
max 240 s
off
(recovery time)
1 red LED for voltage
≥ 50 V AC / 120 V DC
1 green LED for continuity
0 ... 1000 kΩ
1 Display (LCD) with
backlight
measuring rate 2/s
maintenance-free –
without battery
Voltage tests from the
mains
functions continuity/
phase/phase sequence
by integrated Li-accu
CAT IV 600 V / CAT III 690 V
>8 kV (1,2/50 µs)
6 kV
impact resistant, dust proof
ABS plastic casing
Display cover made of
polycarbonate
IP 65
PUR sheated cable
1000 V, 1 m
IEC 61243-3:2009
EN 61243-3:2010
DIN-EN 61243-3:2011
DIN-EN 61326
display part
231 x 48 x 37 mm
170 g
17