Installation Notes - JUMO ER8 Betriebsanleitung

Vorschau ausblenden Andere Handbücher für ER8:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Installation

Installation notes

The choice of cable, the installation and the electrical connection
must conform to the requirements of VDE 0100 "Regulations on
the installation of power circuits with nominal voltages below
1000V", or the appropriate local regulations.
The electrical connection must only be carried out by properly
qualified personnel.
If contact with live parts is possible when working on the instru-
ment, it has to be isolated on both poles from the supply.
The electromagnetic compatibility (EMC) conforms to the stan-
dards and regulations listed under Technical Data.
Run input, output and supply lines separately and not parallel to
each other.
Do not connect additional loads to the supply terminals of the
instrument.
The instrument is not suitable for installation in hazardous areas.
Inductive loads in the vicinity of the instrument, such as contac-
tors or solenoid valves, have to be fitted with RC combinations
for interference suppression.
Connect the screening for the interface cable to the ground of
the external module and to the instrument ground.
Configuration
Instructions and DIP-switches on right side of device.
DIP-switch settings for:
DICON 400/401/500/501
LOGOPRINT 500
LOGOLINE 500
IMAGO 500
Relay Module 1
IMAGO 500
Relay Module 2
The external module must be
configured with DIP switches
for the device it is connected
to.