Herunterladen Inhalt Inhalt Diese Seite drucken

Victron energy MultiPlus 24/3000/70 Anleitung Seite 19

Vorschau ausblenden Andere Handbücher für MultiPlus 24/3000/70:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 71
Step 2: Exemplary settings
Example 1 is the factory setting (since factory settings are entered by computer, all DIP switches of a new product are set to 'off' and do
not reflect the actual settings in the microprocessor).
DS-8 Ch. voltage
off
DS-7 Ch. voltage
on
DS-6 Absorpt. time
on
DS-5 Adaptive ch.
on
DS-4 Dyn. Curr. limit
off
DS-3 UPS function:
on
DS-2 Voltage
on
DS-1 Frequency
on
Step 2
Example 1 (factory setting):
8, 7 GEL 14,4 V
6 Absorption time: 8 hours
5 Adaptive charging: on
4 Dynamic current limit: off
3 UPS function: on
2 Voltage: 230 V
1 Frequency: 50 Hz
To store the settings after the DIP switches are set according to the required values: press the 'Down' button for 2 seconds (lower
button to the right of the DIP switches). The temperature and low-battery LEDs will flash to indicate acceptance of the settings.
The DIP switches can be left in the selected positions, so that the 'other settings' can always be recovered.
18
DS-8
off
DS-8
DS-7
off
DS-7
DS-6
on
DS-6
DS-5
on
DS-5
DS-4
off
DS-4
DS-3
off
DS-3
DS-2
on
DS-2
DS-1
on
DS-1
Step 2
Step 2
Example 2:
Example 3:
8, 7 OPzV 14,1 V
8, 7 AGM 14,7 V
6 Abs. time: 8 h
6 Abs. time: 8 h
5 Adaptive ch.: on
5 Adaptive ch: on
4 Dyn. Curr. limit: off
4 Dyn. Curr. limit: on
3 UPS function: off
3 UPS function: off
2 Voltage: 230 V
2 Voltage: 240 V
1 Frequency: 50 Hz
1 Frequency: 50 Hz
on
DS-8
on
off
DS-7
on
on
DS-6
off
on
DS-5
off
on
DS-4
off
off
DS-3
on
off
DS-2
off
on
DS-1
off
Step 2
Example 4:
8, 7 Tub.-plate 15 V
6 Abs. time: 4 h
5 Fixed abs. time
4 Dyn. Curr. limit: off
3 UPS function: on
2 Voltage: 240 V
1 Frequency: 60 Hz

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Multiplus 12/3000/120Multiplus 48/3000/35

Inhaltsverzeichnis