Model:
FLEXA Series
Installation for Division 2 / Zone 2
Applicable models: FLXA21-D-x-x-CD-xx-xx-F-..., FLXA21-D-x-x-CD-xx-xx-P-...
FLXA21-D-x-x-DD-xx-xx-F-..., FLXA21-D-x-x-DD-xx-xx-P-...
Hazardous (Classified) Location
Class I, Division 2, Groups A, B, C, D, or
Class I, Zone 2, Group IIC,
Temperature Class: T4
FLXA21 Analyzer
Housing Assembly
Measuring Module 1
Sensor 1
(Note 8)
Measuring Module 1 (Note 8):
Type of Measuring Module
pH, SC, DO
Uo
11.76 V
Io
116.5 mA
Po
0.3424 W
Co
4 F
Lo
4.5 mH
Specific condition of use:
- Precautions shall be taken to minimize the risk of non-metallic parts and painted parts of
the enclosure. When the equipment is used in hazardous locations, avoid any action which
generates electrostatic discharge such as rubbing with a dry cloth.
Rev.3: Dec. 26, 2019
Other
Field Devices
Supply +
T
Supply –
Terminators
Supply +, Supply – (Note 9):
Ui: 24 V
Ci: 2.72 nF
Li: 0 mH
ISC
SENCOM
11.76 V
5.36 V
60.6 mA
106.16 mA
0.178 W
0.1423 W
4 F
31 F
19 mH
0.45 mH