Coarse adjustment: Turn switching dial in the direc-
tion of the arrow until the current day of the week is
opposite the marking arrow C.
Fine adjustment: Continue turning the minute
hand in the direction of the arrow until the current
time is opposite the marking arrow C.
The control comes with factory pre-set switching
times. Night setback starts at 10.00 PM (22.00) and
day temperature at 6.00 AM (06.00).
The control is easily re-programmed. The setback
period is changed by pressing the desired amount
of pegs B towards the edge of the programmer.
One peg equals 2 hours. Return to day temperature
occurs at the next unpressed peg. Shortest make-
time is 2 h.
The setback temperature is selected with knob H.
Knob H grading 0°-10°C me¬ans that the supply
water temperature can be lowered by 10°C from
setting 0. 2,5ºC supply water temperature corres-
ponds to 1ºC room temperature.
N.B! With a connected room sensor AM 30 RA/RB
the knob H grading means 0°–10ºC room tempe-
rature.
AUTOMIX 30 D has a digital programmer with day-
and weekly program facility for night setback 8 ti-
mes in a 24 h period. The programmer has 150 h
spring reserve. For setting the digital programmer
see enclosed instruction.
The setback temperature is selected with knob H.
Knob H grading 0°-10°C means that the supply wa-
ter temperature can be lowered by 10°C from set-
ting 0. 2,5ºC supply water temperature correspon-
des to 1ºC room temperature.
N.B! With a connected room sensor AM 30 RA/RB
the knob H grading means 0°–10ºC room tempe-
rature.
Hydronic heating systems and especially floor
heating systems respond slowly to program chan-
ges. After a re-programming it takes one to seve-
ral hours before the new tem¬perature is actually
reached. Consequently, temperature setbacks and
setups should be set 1 to 2 hours earlier than the
desired time.
PROGRAM SELECTOR
Night setback temperature
Day temperature
Automatic day/night setback program
MIN/Summer setting with frost protection
Manual setting
At summer setting with frost protection the pro-
grammer goes. Motor and valve are normally clo-
sed. The MIN. supply water temperature is set with
knob E.
At manual setting the motor does not work. The
pump runs. The valve can now be adjusted manu-
ally.
MIN./MAX. SUPPLY WATER TEMPERATURE
Adjustment of min./max. temperature of the
supply water temperature is used in floor heating
sys¬tems. Min. temperature is adjusted with knob
E and max. temperature with knob G.
RIGHT/LEFT DIRECTION OF MOTOR
Right or left direction of motor is selected with
knob I. Set the the selector at L or R.
The LEDs M and N indicate motor opening and
closing respectively.