INSTALLATION
Controller
The socket is mounted directly on a valve or on a
wall. When mounted on the wall the socket is
cut out. See K below. The controller is placed on the
socket.
Supply water sensor T1
Supply water sensor T1 is fastened on a non-insula-
ted part of the supply pipe 1 m after the mixing val-
ve. For optimum temperature measuring the pipe
has to be insulated afterwards.
1. Turn the spindle of valve A counter clockwise
to the end position (open or closed). Remove
the knob/handle without changing the position
of the spindle. Fasten socket I with screws J
or fasten socket K to the wall.
2. Screw the anti-rotation stop B in a convenient
hole on the valve (if necessary remove an existing
screw).
3. Slide linkage C over the valve spindle. Place
motor D onto linkage C until the anti-
rotation stop B engages in the slot of the motor.
4. The motor is supplied in the anti-clockwise
position. Turn scale E according to the open/closed
direction of the valve.
Outdoor sensor T2
Outdoor sensor T2 is mounted on the north or
north-western outdoor wall at least 3 metres (9
feet) above ground. The outdoor sensor must never
be mounted above a window or near an air valve as
this would influence the sensor.
Room sensor AM 30 RA/RB
Room sensor AM 30 RA/RB (optional) is mounted
at a place with an average temperature of the hou-
se. The room sensor should not be placed where it
can be affected by direct sunshine, heat radiation
or draught. Ra¬diators with thermostatic valves in
the same room as the room sensor must be max.
opened to obtain a correct controlling.
AUTOMIX 52B VALVE MOTOR
5. Place handle F onto the motor ensuring that the
arrow points to the left end position of the scale.
Tighten the whole unit by means of screw G.
6. Using a screwdriver (No.3) turn the disengaging
button H from "A" to "HAND" position and rotate
the valve by means of handle F from one end posi-
tion to the other. It is important that the motor
can be moved from one end stop to the other (90°)
7. Connect the motor wire to the MOTOR-connec-
tion on the control unit.
8. Turn the disengaging button H back to "A" which
is the AUTOMATIC-position.