Automix 30 is an electronic temperature control for
hydronic radiator and radiant floor heating applica-
tions. Automix 30 is ready for mounting and can ea-
sily be integrated in existing heating systems. The
main supply and all sensors have plug-in connec-
tions. The quick and easy do-it-¬your-self installati-
on saves on labor charges.
Automix 30 works continuously and proportionally.
Through impulses from the sensors the con¬troller
directs the motor to keep the valve plug in the po-
sition that corresponds to the present heat require-
ment of the house.
THREE MODELS
• AUTOMIX 30 E Electronic programmer with 24 h
program facility for night setback once in a 24 h
period.
• AUTOMIX 30 Q Quartz programmer with day- and
weekly program facility for night setback 6 times
in a 24 h period. The programmer has 150 h spring
reserve.
• AUTOMIX 30 D Digital programmer with day- and
weekly program facility for night setback 8 times
in a 24 h period. The programmer has 150 h spring
reserve.
DELIVERY PARTS
1. Electronic controller AM 30 E, AM 30 Q or AM
30 D with four LEDs for indication.
2. AUTOMIX 52B valve motor 24 VAC 50/60 Hz
with 1.5 m wire.
3. Supply water sensor T1 with 2 m wire.
4. Outdoor sensor T2 with 15 m wire.
5. Power supply plug-in transformer 230/18
VAC 50/60 Hz 200 mA with 1.7 m wire.
6. Socket.
OPTIONALS
• AM 30 RA room sensor with 15 m wire designed for
AUTOMIX 30 E. The room sensor has settings for pro-
gramming night setback and LEDs for indication.
• AM 30 RB room sensor with 15 m wire designed
for AUTOMIX 30 Q and AUTOMIX 30 D. The room
sensor has LEDs for indication.
• AM 30 RC remote control with 15 m wire for pa-
rallel displacement of regulating graph. AM 30 RC
is used instead of a room sensor. With the remote
control the supply water temperature can be lowe-
red by up to 9ºC and risen by 6°C.
• AM 30 PC pump control with 2 m wire for warm
weather shut down. A LED indicates pump off. An
interval control starts the circulation pump and the
mixing valve for a short time once every 48 h.
CONTROLLER
A. Quartz programmer
B. Pegs
C. Time marking arrow
D. Graph setting
E. Min. supply temperature
F. Parallel displacement of graph
G. Max. supply temperature
H. Temperature setback
I. Right/left direction of motor
J. Yellow LED - temperature setback on
K. Green LED – day temperature on
L. Program selector
M. Red LED - mixing valve opens
N. Red LED – mixing valve closes
1