Permissible current of the connection plug
I
= 10 A for Ta < 60 °C
max
I
= 9 A for Ta < 70 °C
max
Note
Cable cross-sections
The cable diameters must be approved for the required current.
Wiring of the supply voltage
The stripped part of the cable must be inserted completely into the terminal of the Ex
BaseUnit.
Rule for ...
Connectable cable cross-sections
for solid cables
Connectable
without wire end
cable cross-
sleeve
sections for
with wire end
flexible cables
sleeve (with
plastic sleeve)
with TWIN end
sleeve
Stripped length of cables
Wire end sleeves to DIN 46228
with plastic sleeve
* AWG: American Wire Gauge
** Wire end sleeves without plastic sleeve: 1.0 mm
Ex-PM E
A5E50377660-AB, 03/2023
Ex power module (supply voltage)
1.0 to 2.5 mm
2
AWG*: 17 to 13
1.0 to 2.5 mm
2
AWG*: 17 to 13
1.0 to 1.5 mm
**
2
AWG*: 17 to 16
1 mm
2
8 to 10 mm
8 and 10 mm long
to 2.5 mm
2
Ex-PM E
/AWG: 17 to 13
2
11