Følerfejlsdetektering .................................... Ja
Kortslutningsdetektering ............................. Hvis 0% > 30 Ω
TC-indgang:
Min.
Max.
Type
temperatur
temperatur
B
+400°C
+1820°C
E
-100°C
+1000°C
J
-100°C
+1200°C
K
-180°C
+1372°C
L
-100°C
+900°C
N
-180°C
+1300°C
R
-50°C
+1760°C
S
-50°C
+1760°C
T
-200°C
+400°C
U
-200°C
+600°C
W3
0°C
+2300°C
W5
0°C
+2300°C
Koldt loddestedskomp. (CJC) ..................... < ±1,0 °C
Ekstern CJC med Ni100 eller Pt100 ........... -40 ≤ T
Følerfejlsdetektering .................................... Ja
Følerfejlsstrøm:
under detektering ................................. Nom. 33 µA
ellers ..................................................... 0 µA
Kortslutningsdetektering ............................. Hvis 0% > 5 mV
Spændingsindgang:
Måleområde ................................................ -800...+800 mV
Min. måleområde (span) .............................. 2,5 mV
Indgangsmodstand ..................................... 10 MΩ
Strømudgang:
Signalområde .............................................. 4...20 mA
Min. signalområde ....................................... 16 mA
Opdateringstid ............................................. 440 ms
Fast udgangssignal ..................................... Mellem 4 og 20 mA
Udgangssignal ved EEpromfejl ................... ≤ 3,5 mA
Belastningsmodstand .................................. ≤ (V
Belastningsstabilitet .................................... < ±0,01% af span / 100 Ω
Følerfejlsdetektering:
Programmerbar ........................................... 3,5...23 mA
NAMUR NE43 Upscale ............................... 23 mA
NAMUR NE43 Downscale ........................... 3,5 mA
8
Min.
span
Norm
100°C
IEC584
50°C
IEC584
50°C
IEC584
50°C
IEC584
50°C
DIN 43710
50°C
IEC584
100°C
IEC584
100°C
IEC584
50°C
IEC584
50°C
DIN 43710
100°C
ASTM E988-90
100°C
ASTM E988-90
≤ 135°C
omg.
(660 ms for diff.)
- 8) / 0,023 [Ω]
forsyn.
Ex- / I.S.-data:
Signaludgang / forsyning, terminal 1 til 2:
U i ................................................................. : 30 VDC
I i .................................................................. : 120 mADC
P i ................................................................. : 0,84 W
L i ................................................................. : 10 µH
C i ................................................................. : 1,0 nF
Følerindgang, terminal 3, 4, 5 og 6:
U o ............................................................... : 9,6 VDC
I o ................................................................. : 28 mA
P o ................................................................ : 67 mW
L o ................................................................ : 35 mH
C o ................................................................ : 3,5 µF
EEx- / I.S-godkendelse 5335A:
KEMA 03ATEX1508 X ..................................
EEx- / I.S.-godkendelse 5335B, C og D:
KEMA 03ATEX1537 X ..................................
Max. omgivelsestemp. for T1...T4 .............. 85°C
Max. omgivelsestemp. for T5 og T6 .......... 60°C
ATEX, må anvendes i zone .......................... 0, 1, 2, 20, 21 eller 22
FM, må anvendes i ...................................... IS, Class I, DIV. 1, Group A, B, C, D
Entity, FM Installation Drawing No. ............. 5300Q502
CSA, må anvendes i .................................... IS, Class I, DIV. 1, Group A, B, C, D,
Installation Drawing No. .............................. 533XQC03
Marine-godkendelse:
Det Norske Veritas, Ships & Offshore ......... Standard for Certification No. 2.4
Overholdte myndighedskrav:
EMC 2004/108/EF
Emission og immunitet ....................... EN 61326
ATEX 94/9/EF .............................................. EN 50021, EN 50014, EN 50020
FM, ASCN ................................................... 3600, 3611, 3610
CSA, CAN / CSA ......................................... C22.2 No. 157, E60079-11, UL 913
Af span = Af det aktuelt valgte område
II 3 GD
EEx nA[L] IIC T4 eller T6
II 1 GD, T80°C...T105°C
EEx ia IIC T6 / T4
IS, Class I, Zone 0, AEx ia IIC
Ex ia IIC
IS, Class I, Zone 0, AEx ia IIC
Standard:
EN 50284 og EN 50281-1-1
9