ATEX - approval DEKRA 21ATEX0010X
Type Examination Certificate Number
Standards
Marking
The certificate is valid for the "Certificate (https://support.industry.siemens.com/cs/ww/en/view/109475140)" products listed
in the certificate.
Special conditions
The device may only be used in areas with a pollution degree of no more than 2 according to EN 60664-1.
The modules must be set up in a suitable enclosure that guarantees at least IP54 degree of protection according to
EN 60079-0 taking into account the ambient conditions during use.
Measures must be taken to prevent exceeding the rated voltage by more than 119 V of transient disturbance voltages.
IECEx - approval IECEx DEK 21.0008X
Certificate number
Standards
Marking
The certificate is valid for the "Certificate (https://support.industry.siemens.com/cs/us/en/view/109795939)" products listed
in the certificate.
Special conditions
The device may only be used in areas with a pollution degree of no more than 2 according to IEC 60664-1.
The modules must be set up in a suitable enclosure that guarantees at least IP54 degree of protection according to
IEC 60079-0 taking into account the ambient conditions during use.
Measures must be taken to prevent exceeding the rated voltage by more than 119 V of transient disturbance voltages.
UKEx - approval DEKRA 21UKEX0018X
Certificate number
Standards
Marking
The certificate is valid for the "Certificate (https://support.industry.siemens.com/cs/ww/en/view/109805346)" products listed
in the certificate.
Special conditions
The device may only be used in areas with a pollution degree of no more than 2 according to EN 60664-1.
The modules must be set up in a suitable enclosure that guarantees at least IP54 degree of protection according to
EN 60079-0 taking into account the ambient conditions during use.
Measures must be taken to prevent exceeding the rated voltage by more than 119 V of transient disturbance voltages.
CCC approval
Ex ec IIC T4 Gc
Ex ec IIC Gc
16
Certificate:
2020322309002744
DEKRA 21ATEX0010X
EN IEC 60079-0
EN IEC 60079-7 + A1
II 3 G
Ex ec IIC T4 Gc
IECEx DEK 21.0008X
IEC 60079-0
IEC 60079-7
Ex ec IIC T4 Gc
DEKRA 21UKEX0018X
EN IEC 60079-0
EN IEC 60079-7 + A1
II 3 G
Ex ec IIC T4 Gc
CPU 410 Process Automation