Over-Current Setting (Menu option F3 in display)
ATTENTION: The over-current setting is set automatically during the learning run. An adjustment via the menu is
usually not necessary.
The factory-set forces (value 25) are designed to provide a smooth operation of the opener with standard swing
gates; the factory setting forces should be, in principle, sufficient to fully open and close the gate. The factory setting
of the operator complies with the legal or relevant standards (such as the EN 13241-1, EN 12453, EN 60335-2-95)
established requirements for operational forces, and thus the maximum allowable power limits. If necessary, the
operating force of the operator may be increased or decreased (values 01 - 45) by the following procedure
described below.
NOTE
This must be done, for example, if one of the end positions "gate open" or "gate closed" is not reached via the
factory setting (value 25). Then, the setting for the maximum force, as described below, may be gradually increased
until both end positions are reached.
In addition, during the operational period of the gate, the operational optimality may deteriorate. Therefore, for safety
reasons, adjusting force of the operator on an unsound gate could result in a malfunctioning gate, thus increasing
the risk of personal injury or property damage -- this risk is especially increased when activating the manual release
of the garage door from the operator.
DANGER
Deviating/Increasing the factory force setting (value 25) can lead to serious personal injury, up to the danger of life
as well as property damage! Altering the factory force setting increases the pressure exerted by the operator when
opening and closing gate, thus increasing the force that the gate exerts in each respective phase. When changing or
differing from the factory settings, the risk of severe injury to persons up to the danger of life as well as the risk of
damage to property is increased - for example, by pinching or squeezing persons or things near the gate. Differing
from the factory settings, increasing the power setting to exceed the aforementioned maximum allowable limit can
cause power limitations. Therefore:
NOTE:
After each setting of the force (values 01 to 45) deviating from the factory setting (value 25), compliance
with the force limit values required by law or in the relevant standards must be checked, accepted,
measured and documented by a qualified person to exclude the aforementioned dangers to life and limb
and property damage.
Photocell as additional safety device
In order to ensure safe operation of the gate system, it is absolutely necessary to install and activate the supplied
photocell safety beam and keep it activated. Operation without a photocell can lead to serious injuries to persons
and animals, even to life, as well as damage to property.
Adjusting the Reversing Limit (Menu FI/ FJ)
For the settings FI and FJ, the parameters are different depending on which motor type setting (setting F1) is
activated. Setting F1-3 is the factory setting, therefore the factory setting governing the reverse when closing (FI) is:
Reverse to the end for not detecting hall sensor or over-current occurs before reaching closing position. Meaning
the motor will reverse to the end when encountering an object. The factory setting governing the reverse when
opening (FJ) is: Reverse 2 seconds when not detecting hall sensor or over-current occurs before reaching closing
position. Meaning the motor will reverse for 2 seconds when encountering an object. In the factory setting, the drive
fulfills the statutory or relevant requirements of the standards.
These settings are different when switching the motor to setting F1-1 - please see page 30 to see the parameters
while in this motor type.
According to any setting deviating from the factory setting, compliance with the reversing limits
required by law or the relevant standards must be checked, measured, and documented by a competent person in
order to rule out the dangers for life and property.