Herunterladen Inhalt Inhalt Diese Seite drucken

ABB ACS880-14 Schnellinstalationsanleitung Seite 15

Vorschau ausblenden Andere Handbücher für ACS880-14:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 43
Connect the external control cables to the control unit
See
Connecting the external control cables to the control unit (page 289)
Step
Tasks
1
Connect the intermediate control cables between the control unit and the drive module as
follows:
• Remove the plate which covers the slot in the middle front cover of the drive module at
the front or left side.
• Install a rubber grommet (item 6 in the accessories box) to the slot.
• Route the cables through the slot.
• Connect the power supply cable to terminal X2.
• Connect the STO cable to the INU STO connector.
• Connect the fiber optic cables to the QOIA V8, V13, V2 and V7 connectors.
I S U p a n e l
C a t 5 c a b l e
Note: ISU ext. 24VDC connector is for supplying external 24 V DC to the line-side converter
control unit if needed. ISU panel connector is for connecting the control panel to the line-
side converter control unit if needed.
2
Disconnect the control panel cable from connector X13 on the control unit.
3
Loosen the mounting screws of the control panel holder and take the holder off.
4
Install the control cable grounding clamp plate to the control unit.
EN – Quick installation and start-up guide 15
QOIA
INU STO
V13
ZBIB
X7 (STO1)
X8 (STO2)
X2
X3
V2
V2
V7
V1
V8
V21
V22
EN
DA
DE
ES
FI
FR
IT
NL
PL
PT
SV
TR
ZH

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Acs880-34

Inhaltsverzeichnis