6. Checkout and service

6.1 Checkout
1. Raise the set point of the zone thermostat above
room temperature to initiate a call for heat. White
valve position lever should move.
2. For auxiliary switch models, observe all control
devices. The valve should open and the auxiliary
switch (if present) should close and make at the end
of the opening stroke to activate auxiliary equip-
ment.
3. Lower the set point of the zone thermostat below
room temperature.
4. Observe the control devices. The valve should close
and all auxiliary equipment should stop.
www.honeywell.com
Table 2: Electrical termination - contacts function
Cable models
Wire Colour
(See Fig. 7)
Brown
Black
Blue
White
Orange
Grey
3
6
L
M
2
N
PORT 'A'
SW1
SW2
Cam
GB
MOLEX™ models
(See Fig. 8)
3
6
2
5
1
4
5
1
4
Fig. 8: VC Actuator with Molex™ connector for
SPDT Controller
3
Brown / Marrone / Marrón
Close / Chiude / Se cierra
Controller
SPST
Open / Apre / Se abre
6
Black / Nero / Negro
L
N
2
Blue / Blu / Azul
Fig. 10: VC Actuator for SPST Controller
Service
This valve should be serviced by a trained, experi-
enced service technician.
1. If the valve is leaking, drain system OR isolate valve
from the system. Do not remove body from plum-
bing.
2. Check to see if the cartridge needs to be replaced.
3. If the motor or other internal parts of the actuator is
damaged, replace the entire actuator assembly
Note: Honeywell hydronic valves are designed and
tested for silent operation in properly designed
and installed systems. However, water noises
may occur as a result of excessive water
velocity. Piping noises may occur in high tempe-
rature (100°C) systems with insufficient water
pressure.