LINETRAXX® RCM410R-24/-2
Technische Daten
Versorgungsspannung
RCM410R-24:
Versorgungsspannung U
........................................................ DC 24 V
s
Toleranz von U
..............................................................-30...+25 %
s
Eigenverbrauch ......................................................................... ≤ 2 W
RCM410R-2:
Versorgungsspannung U
................AC/DC 100...240 V (47...63 Hz)
s
Toleranz von U
........................................................................ ±15 %
s
Eigenverbrauch ....................................................... ≤ 2 W / ≤ 3,5 VA
Messkreis
Messstromwandlertyp ........................................................................
..............................................CTAC..., W..., WF...*, WR..., WS...
* Einsatz nur bei deaktivierter Messstromwandler-Anschlussüberwachung am
RCM410R möglich.
Bürde ...........................................................................................33 Ω
Ansprech-Charakteristik ............................................................. Typ A
Bemessungsspannung U
...........siehe Datenblatt Messstromwandler
n
Frequenzbereich ............................................................... 42...70 Hz
Messbereich RMS ............................................................2 mA...50 A
Ansprechdifferenzstrom I
...........................................10 mA...30 A
Δn
Betriebsmessabweichung ...........................±10 % (bei 0,5...5 x I
Prozentuale Ansprechunsicherheit ................................... 0...–20 %
Kontaktdaten nach IEC 60947-5-1:
Gebrauchskategorie .................AC 13 / AC 14 / DC-12 / DC-12 / DC-12
Bem.betriebsspannung ............... 230 V / 230 V / 24 V / 110 V / 220 V
Bem.betriebsstrom .................................5 A / 3 A / 1 A / 0,2 A / 0,1 A
Min. Kontaktbelastbarkeit ...........................1 mA bei AC/DC ≥ 10 V *
* bezieht sich auf Relais, die noch nicht mit hohen Kontaktströmen betrieben
wurden
Anschluss
Anschlussart ............................................................................ Push-In
Anschlussvermögen
starr .................................................. 0,2...1,5 mm² (AWG 24...16)
flexibel ohne Aderendhülse ............... 0,2...1,5 mm² (AWG 24...16)
flexibel mit Aderendhülse und Plastikhülse ...............0,2...0,75 mm²
flexibel mit Aderendhülse ohne Plastikhülse ............0,2...1,5 mm² *
* > 0,75 mm² nur Crimpzange ähnlich CRIMPFOX 6 / Weidmüller PZ6/PZ6/5
verwenden.
Alle Rechte vorbehalten.
Nachdruck und Vervielfältigung
nur mit Genehmigung des Herausgebers.
Bender GmbH & Co. KG
Postfach 1161 • 35301 Grünberg • Deutschland
Londorfer Str. 65 • 35305 Grünberg • Deutschland
Tel.: +49 6401 807-0 • Fax: +49 6401 807-259
E-Mail: info@bender.de • www.bender.de
Technical data
Supply voltage
RCM410R-24
Supply voltage U
.................................................................... DC 24 V
s
Tolerance U
...................................................................-30...+25 %
s
Power consumption .................................................................. ≤ 2 W
RCM410R-2
Supply voltage U
............................AC/DC 100...240 V (47...63 Hz)
s
Tolerance U
............................................................................. ±15 %
s
Power consumption .................................................≤ 2 W / ≤ 3.5 VA
Measuring circuit
Measuring current transf. type ...........................................................
..............................................CTAC..., W..., WF...*, WR..., WS...
* Can only be used when CT connection monitoring is disabled on the
RCM410R.
Load .............................................................................................33 Ω
Operating characteristics ..........................................................Type A
Rated voltage U
..........see datasheet measuring current transformer
n
Frequency range ..............................................................42...70 Hz)
Measuring range RMS .....................................................2 mA...50 A
Residual operating current I
Operating uncertainty ...................................±10 % (at 0.5...5 x I
)
Δn
Relative uncertainty .......................................................... 0...–20 %
Contact data acc. to IEC 60947-5-1:
Utilisation category ..................AC 13 / AC 14 / DC-12 / DC-12 / DC-12
Rated op. voltage ........................ 230 V / 230 V / 24 V / 110 V / 220 V
Rated op. current. ...................................5 A / 3 A / 1 A / 0.2 A / 0.1 A
Minimum contact rating ................................1 mA at AC/DC ≥ 10 V *
* refers to relays that have not been operated with high contact currents.
Connection
Connection type ...................................................................... push-in
Connection properties
rigid ................................................... 0.2...1.5 mm² (AWG 24...16)
flexible without ferrule ...................... 0.2...1.5 mm² (AWG 24...16)
flexible with ferrule and plastic ferrule ......................0.2...0.75 mm²
flexible with ferrule without plastic ferrule .............0.2...1.5 mm² *
* > 0.75 mm² use crimping pliers simlar CRIMPFOX 6 / Weidmüller PZ6/PZ6/5
only.
......................................10 mA...30 A
Δn