6.2.3 Wiring

Wiring inside the Smart Home Panel
All wires come labeled in the box, 12 input wires, labeled "1 in - 10 in" "Pro1 in, Pro2 in" connected to the
circuit breakers, 10 output wires, labeled "1 out - 10 out" connecting to the load hot wires, two neutral
wires connecting to the neutral bus bar in the main panel and ground wire connecting to the ground
bus bar in the main panel. Users should connect all input, output, neutral and grounds wire to their
designated connectors inside the SHP.
Input connectors
Pro1,N1,N2,Pro2
NOTE
Two neutral wires and the ground wire must be connected to the main panel in order for the SHP to
operate correctly and safely.
The maximum current for circuits 1-4 is 30A. Maximum current for circuits 5-10 is 20A. The current
rating for each circuit should not be exceeded. Please plan the load circuits appropriately. If a non-
metallic conduit is used to connect between the main panel and SHP, an equipment grounding
conductor needs to be present inside each conduit. Additional ground wires can be connected
between the ground bar inside the main panel and the SHP.
You may use your own wires with the connectors instead of the included wire. Use a screwdriver to
remove the connectors, strip the wire and then insert and torque down
15