TROUBLESHOOTING
Warning: Before any maintenance or repair activities, make sure that the power supply is cut off and cannot be
!
turned on by accident.
Issue:
The pump fails to launch
Loud system operation
Loud pump operation
UTILISATION
The used product is subject to disposal as wastes only in selective waste collection systems organised
by the Network of Communal Electric and Electronic Waste Collection Centres. The customer is
entitled to return the used equipment to the network of the electric equipment distributor, at least for
free and directly, if the returned device is of proper type and fulfils the same function as a newly purchased device. It is
prohibited to dispose of electric equipment together with other household waste.
EC DECLARATION OF CONFORMITY (Moduł A):
1.Circulating pumps MAGI 2 25-40/180, MAGI 2 25-60/180, MAGI 2 25-60/130,
2. PHU Dambat, Gawartowa Wola 38, 05-085 KAMPINOS, POLAND, e-mail:
3.
This declaration of conformity is issued under the sole responsibility of the manufacturer.
4. Pumps form point 1.
5. We declare with full responsibility that pumps included in the point 1. to which this declaration refers to are
consistent with the following guidelines of the Council on legal regulations unification in member states of EC:
-Directive EMC No. 2014/30/EU
-Directive LVD No. 2014/35/EU
- Directive MD No. 2006/42/EC
-Directive ErP No. 2009/125/EC.
6. Applied standards:
EN 60204-1:2006+A1:2009+AC2010, EN 809:1998+A1:2009+AC:2010, EN 62233:2008, EN 16277-
1:2012, EN 16277-2:2012, EN 16277-3:2012, EN 60335-1:2012+A11:2014+A13:2017,
EN 60335-2-41:2003+A1:2004+A2:2010, EN 55014-1:2017, EN5014-2:2015, EN 61000-3-2:2019,
EN 61000-3-3:2013+A1:2019
USE AND CARE GUIDE MAGI 2
Possible cause:
Tripped installation fuse
Overcurrent circuit breaker switched off
Pump damaged
Voltage too low
Pump rotor blocked
Air in the installation
Flow too high
Air in the pump
Inflow pressure too low - cavitation
Pump parameters too low
Solution:
Check the cause, replace the fuse
Start the breaker
Replace the pump
Check if the main voltage
is compliant with the supplier's
specification
Unlock the rotor
Vent the installation
Decrease the inflow pressure at
the pump inlet
Vent it
Increase the inflow pressure at the inlet to
the pump
If possible, increase the pump operation
mode into a more efficient one, otherwise
install stronger pump
biuro@dambat.pl
Gawartowa Wola 23.11.2018
Adam Jastrzębski
21