Herunterladen Inhalt Inhalt Diese Seite drucken

IBO MAGI 2 25-40/180 Betriebsanleitung Seite 15

Energiesparende umwälzpumpe
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

INSTALLATION
In installation, please pay attention to the flow direction of the heating medium. An arrow on the pump body shows
the flow direction forced by the pump. That direction must be compliant with the circulation of the medium in the
system.
- In installation, please use the bolts with rubber sealing included in the set.
- The pump should be installed in such a way that the pump shaft is horizontal
P
ermissible positioning of the control panel
Change in arrangement of the control panel
The control panel along with the motor corpus can rotate every 90°. To change the position of the junction box,
perform the following activities:
1. Disconnect the pump from power supply.
2. Close the cut off valves at the inflow and outflow of the pump and perform decompression;
3. Loosen and remove four bolts fixing the head in the pump body;
4. Rotate the motor into the desired position and fit four openings for bolts;
5. Insert four ampoule head screws to proper sockets and tighten
WARNING!!!
T he heating medium can ha v e high temper ature and pressure, therefore it is necessary to
!
discharge the liquid from the system or close the cut-off valves on both sides of the pump before the ampoule
head screws are removed.
After the position of the pump control panel is changed, do not start it before the heating system is
refilled with the heating medium or before the cut-off valves before and after the pump are opened.
USE AND CARE GUIDE MAGI 2
them;
15

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Magi 2 25-60/130Magi 2 25-60/180

Inhaltsverzeichnis