Modbus
Register
adress
40022
ON/OFF_Active_State
40023
BOOST_Active_State
40024
MIN/MAX_Active_State 16 BITS
Operation modes
40027
OPERATION_MODE
VAV mode
40030
AI1_CONFIG
40031
SETPOINT_prop_AI1
40032
AI1_Band
40033
AI1_Sensor_out_min
40034
AI1_Sensor_out_max
40035
Speed_prop_to_sensor 16 BITS
40036
AI1_Filter
40037
AI1_alarm_limit
40038
AI1_alarm_delay
40041
AI2_CONFIG
40042
SETPOINT_prop_AI2
40043
AI2_Band
40044
AI2_Sensor_out_min
40045
AI2_Sensor_out_max
40046
Speed_prop_to_sensor 16 BITS
40047
AI2_Filter
Data
Range
type
CRHB/CRVB N
CRHT/CRVT N
ECOWATT PLUS
16 BITS
0 – 1
16 BITS
0 – 1
0 – 1
16 BITS
0 – 5
16 BITS
0 – 4
16 BITS -32000 – 32000
Humidity: 40
Temperature: 10
16 BITS -32000 – 32000
CO2/VOC: 1000
0-10/4-20: 10% of scale
16 BITS -32000 – 32000
16 BITS -32000 – 32000
0 – 1
16 BITS
0 – 3
16BITS
0 – 100
16BITS
0 – 60
16 BITS
0 – 4
16 BITS -32000 – 32000
Humidity: 40
Temperature: 10
16 BITS -32000 – 32000
CO2/VOC: 1000
0-10/4-20: 10% of scale
16 BITS -32000 – 32000
16 BITS -32000 – 32000
0 – 1
16 BITS
0 – 3
Default
Description
ON/OFF
0
0: Normally open (NO)
1: Normally close (NC)
BOOST
0
0: Normally open (NO)
1: Normally close (NC)
MIN/MAX
0
0: Normally open (NO)
1: Normally close (NC)
Opeation mode:
0: Motor off
1: COP
1
2: CAV
3: VAV
4: MIN/MAX
5: Constant speed
Analog input AI1 configuration:
0: Disable
1: Humidity sensor (%)
0
2: Temperature (ºC)
3: CO2/VOC (ppm)
4: 0-10V/4-20mA (another parameters)
0
Setpoint VAV mode. Units depending input configuration
Band VAV mode
0
Equivalent physical units when 0v/4mA of analog input AI1
Equivalent physical units when 10v/40mA of analog input
2000
AI1
0: Variable inversely proportional to speed
1
1: Variable proportional to speed
Filtration grade of AI1
0: None
1
1: Low (high sensitive to AI1 variation)
2: Medium
3: High (low sensitive to AI1 variation)
100
Limit in percentage of AI1 input to generate IAQ alarm
10
Time (minutes) to activate alarm once reached the limit
Analog input AI2 configuration:
0: Disable
1: Humidity sensor
0
2: Temperature
3: CO2/VOC (ppm)
4: 0-10V/4-20mA (another parameters)
0
Setpoint VAV mode. Units depending input configuration
Band VAV mode
0
Equivalent physical units when 0v/4mA of analog input AI2
Equivalent physical units when 10v/40mA of analog input
2000
AI2
0: Variable inversely proportional to speed
1
1: Variable proportional to speed
Filtration grade of AI2:
0: None
1
1: Low (high sensitive to AI1 variation)
2: Medium
3: High (low sensitive to AI1 variation)