Electrical connection

Connect the sensors to the terminals. The sensors can be sup-
plied via an external NON PELV voltage source.
Connection
A+:
AS-i +
A-:
AS-i -
I+:
sensor supply +24V
I-:
sensor supply 0V
E+:
external sensor supply +24V
E-:
external sensor supply 0V
I1 ... I4: switching inputs sensors 1 ... 4
LEDs 1: switching status indication
inputs
LEDs 2: AS-i, FAULT, AUX
LEDs 3: switching status indication
actuator outputs
ADR:
addressing socket
Operation
Check the safe functioning of the unit. Display by LEDs:
• LED green: voltage supply via the AS-i network O.K. or external
power supply o.k.
• LED yellow: input/output switched
• LED red is lit: AS-i communication error, e. g. slave address 0
• LED red flashing: peripheral fault, e.g. no auxiliary voltage

Technical data

You can download the data sheet from the Internet if required
(www.ifm-electronic.com).
LEDs 1
LEDs 2
ADR
LEDs 3
O1
O2
12 14
22 24
11
I- I- E+
E-
I1 I2 I3 I4
I+ I+ I+ I+
14 11 11 12
24 21 21 22
A+ A-
21
6