Technical data Modbus
Bus system
Transmission rate
Transmission mode
Bus length (max.)
Response time:
(to system response)
The communication is ready 30 s after the power on
The use of energy meter in bus with intensive communication could reduce the performance of the bus
Refresh time for the data is 5 s. For this reason one energy meter should be not polled faster as 5 s
247 devices could be connected to the Modbus. With more than 128 devices, a repeater should be used
The interface don't have a terminal resistor, this must be provided external
For a description of the used registers please look at the register page

Data transmission

Only «Read Holding Registers [03]/ Write Multiple Registers [16]» instructions are recognized.
Up to 20 Registers can be read at a time.
The device supports broadcast messages.
In accordance with the Modbus protocol, a register R is numbered as R - 1 when transmitted.
The device has a voltage monitoring system. In case of voltage loss, registers are stored in EEPROM (transmission rate,
etc.)

Exception Responses

ILLEGAL FUNCTION [01]: The function code is not implemented.
ILLEGAL DATA ADDRESS [02]: The address of some requested registers is out of range
or more than 20 registers have been requested.
ILLEGAL DATA VALUE [03]: The value in the data field is invalid for the referenced register.
Changing the Modbus direct on device
In the menu, go for «U»
Push long ( ≥ 3 sec) «Adr»
Push short "address +1", push long "address +10"
Once the desired address is selected wait, to validate, till the root menu to come back
Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Rolle, Z.A. La Pièce 16,
Switzerland by its Authorized Representative:
Saia-Burgess Controls AG
Route Jo-Siffert 4
1762 Givisiez / Switzerland
Phone
+41 26 580 30 00
Fax
+41 26 580 34 99
Subject to change without notice.
Modbus, RTU according to IDA specification
4800-9600-19 200-38 400-57 600-115 200.
The transmission Baud rate is automatically detected
Even parity: 8 data bits, 1 stop bit
Odd parity: 8 data bits, 1 stop bit
No parity: 8 data bits, 2 stop bits
The transmission Mode is automatically detected
1200 m (without repeater)
Write:
up to 60 ms
Read:
up to 60 ms