Technical data Modbus
Bus system
Transmission rate
Transmission mode
Bus length (max.)
Response time:
(to system response)
The Interface works only if the Phase 1 is connected.
The communication is ready 30s after the Power On
The use of Energy meter in Bus with intensive communication could reduce the performance of the Bus
Refresh Time for the Data is 10 s. For this reason one energy meter should be not polled faster as 10s.
247 devices could be connected to the Modbus. Over 128 Devices, a repeater should be used.
The Interface don't have a terminal resistor, this should be provided external.
For a description of the used registers please look at the Register Page.

Data transmission

Only «Read Holding Registers [03]/ Write Multiple Registers [16]» instructions are recognized.
Up to 20 Registers can be read at a time.
The device supports broadcast messages.
In accordance with the Modbus protocol, a register R is numbered as R - 1 when transmitted.
The device has a voltage monitoring system. In case of voltage loss, registers are stored in EEPROM
(transmission rate, etc.)

Exception Responses

ILLEGAL FUNCTION [01]: The function code is not implemented.
ILLEGAL DATA ADDRESS [02]: The address of some requested registers is out of range
or more than 20 registers have been requested.
ILLEGAL DATA VALUE [03]: The value in the data field is invalid for the referenced register.
Change the Modbus address direct on device
To modify the Modbus address, press 3 sec on ► touch
In menu, ▼ increase address by 10, ► increase by 1
Once the address is selected wait for the root menu to come back
Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Rolle, Z.A. La Pièce 16,
Switzerland by its Authorized Representative:
Saia-Burgess Controls AG
Bahnhofstrasse 18
CH-3280 Murten / Switzerland
Phone
Fax
Subject to change without notice. Printed in Switzerland
Modbus, RTU according to IDA specification
4800-9600-19 200-38 400-57 600-115 200.
The transmission Baud rate is automatically detected
Even parity: 8 data bits, 1 stop bit
Odd parity: 8 data bits, 1 stop bit
No parity: 8 data bits, 2 stop bits
The transmission Mode is automatically detected
1200 m (without repeater)
Write: 60 ms
Read: 60 ms