Herunterladen Inhalt Inhalt Diese Seite drucken

Fluke 3563 Erste Schritte Seite 41

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Getting started with Analysis Vibration Sensor System
How Sensor works
The digitized vibration measurements are processed either as overall values or as raw
data.
The gateway can be triggered from Accelix™ to instruct the sensor to record a time
waveform signal. This raw signal is then transferred via the gateway and back to the
Data Platform.
Another portion of the raw signal is converted to overall values, then compared with
the overalls threshold values. If the threshold values are exceeded, an alarm signal
is sent to the gateway. The gateway will then send a request to the sensor to transfer
the overall values causing the alarm signal.
If there is no alarm signal, the overall values are saved in the sensor.
This broadband overall measurement is referred to as screening measurement, and is
triggered within the sensor to be carried out after a set number of minutes, say every
10 minutes.
Hardware Description
The base of the sensor comprises three strong magnets and a cylindrical stainless
steel disc, which are used to attach the sensor to a specially designed mounting
adapter.
The top of the sensor has an LED that shows the wireless connection status between
the sensor and the gateway.
The sensor is powered using six 3.6 V 1/2 AA lithium batteries (use LS 14250 from
Saft) where one battery is a standby battery. The standby battery is used in
case the capacity of the five main batteries falls below required level. It is
recommended to replace all six batteries at the same time. Batteries are
replaced by screwing open the housing.
38

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

3503

Inhaltsverzeichnis