Herunterladen Inhalt Inhalt Diese Seite drucken

Kobold MIM K29 Bedienungsanleitung Seite 68

Inhaltsverzeichnis

Werbung

MIM-
Index
Name
[hex]
0x0122
OUT1Alarm
Suppression
Direction
0x0123
OUT1Analog
NamurStandard
0x0124
OUT1AnalogValue
0mA
0x0128
OUT1AnalogValue
4mA
0x012C
OUT1AnalogValue
20mA
0x0130
OUT1AnalogValue
0V
0x0134
OUT1AnalogValue
2V
0x0138
OUT1AnalogValue
10V
0x013C
OUT1PulseVolume
Seite 68
Description
Factory default
for which direction
0
the suppression
factor is used
If enabled (1) the
1
analog output
conforms with the
NAMUR Standard
NE42. If disabled (0)
the analog output
stays in his
equivalent range
(e.g. 4-20mA)
The value from the
0,0
slot used for the
0mA scaling point
[LPM/°C]
The value from the
0,0
slot used for the
4mA scaling point
[LPM/°C]
The value from the
100,0
slot used for the
20mA scaling point
[LPM/°C]
The value from the
0,0
slot used for the 0V
scaling point
[LPM/°C]
The value from the
0,0
slot used for the 2V
scaling point
[LPM/°C]
The value from the
100,0
slot used for the 10V
scaling point
[LPM/°C]
The volume
1,0
represented by one
pulse [L]
Max Value
Min Value
Length
[Bytes]
(0) - Up
1
(1) - Down
(2) - Both
(0) - NAMUR disabled
1
(1) - NAMUR enabled
OUT1
MRS
4
Analog
Value20mA
OUT1
MRS
4
Analog
Value20mA
MRE
OUT1
4
Analog
Value0mA
OUT1
MRS
4
Analog
Value10V
OUT1
MRS
4
Analog
Value10V
MRE
OUT1Analog
4
Value0V
999,999
0,000001
4
MIM K29/0521
Data Type
Access
UIntegerT
R/W
UIntegerT
R/W
FloatT
R/W
FloatT
R/W
FloatT
R/W
FloatT
R/W
FloatT
R/W
FloatT
R/W
FloatT
R/W