Requirements for the installation surface and location

Installation surface requirements
load capacity, fitness for use, durability in accordance with DIN EN 206
g
evenness tolerance in accordance with DIN 18202 Table 3 Line 3
g
concrete strength minimum C25/30
g
no slope towards the foundation
g
absorbent surfaces or underlying elements cause significant corrosion – DENIOS accepts no liability in this case
g
the product may be anchored
g
Installation location requirements
installation location is outdoors
g
installation location is only accessible by authorised personnel
g
an Ex zone may need to be observed at the installation location
g
no snow drifts can form on the product
g
forklifts and other transport vehicles and lifting equipment cannot drive into the product
g
position away from internal roadways or use impact protection
g
ensure that no nearby heat sources can heat up the product's surfaces
g
install well away from pits, drains or outflows as well as low-lying areas
g
install away from rescue routes
g
fire extinguisher is available and easily accessible
g
Structural requirements
Minimum distances must be observed when storing acutely toxic gases (H330) or flammable gases (H221–220):
5 m around the pressurised gas cylinders to nearby plant or equipment;
g
the minimum distance can be replaced by a 2 m high protective wall in a non-combustible structural material
5.2

Adjusting the product

The product is correctly set up when it is perpendicular to the ground. Check the installation using a suitable tool (e.g.
spirit level).