11 IIoT-Funktionalität
Name
Datentyp
iol
IOL Object
iol/diagGateway
array of DIAG
iol/diagMaster
array of DIAG
iol/ports
array of PORT (8)
CHANNEL
Object
name
string
type
number
type_text
string
config
number
config_text
string
inputState
boolean
outputState
boolean
Handbuch PROFINET
Version 2.0 03/2022
Beschreibung
Contains all IO-Link related information
such as events, port states, device
parameters.
Array of currently active device/
gateway related events
Array of currently active IOL-Master
related events
Contains one element for each IO-Link
port
Name of channel
Hardware channel type as number:
0 = DIO
1 = Input
2 = Output
3 = Input/Output
4 = IO-Link
5 = IOL AUX
6 = IOL AUX with DO
7 = IOL AUX with DO. Can be
deactivated.
8 = Channel not available
Textual representation of the channel
type
Current configuration of the channel:
0 = DIO
1 = Input
2 = Output
3 = IO-Link
4 = Deactivated
5 = IOL AUX
Textual representation of the current
config
Input data (producing data) bit to the
PLC
Output data bit to the physical output
pin
11.3 REST API