9.2 Prozessdaten der IO-Link-Ports,
Slot 1.2 – 1.9
Bit
Acronym
0
1
2
NewParam
3
SubstDev
4
PortActive
5
DevCom
6
DevErr
7
PQ
Tabelle 36: PQI-Beschreibung
140
Short Description
Reserved
Reserved
New parameter
Substitute Device
detection
Port operation
Device communication
Port/Device error
indication
Device Process Data
validity
9 Zuweisung der Prozessdaten
Value
Description
0
Reserved
0
Reserved
0
Not supported yet, don't evaluate
this bit!
1
Not supported yet, don't evaluate
this bit!
0
Not supported yet, don't evaluate
this bit!
1
Not supported yet, don't evaluate
this bit!
0
port deactivated via port function
1
port activated (default)
0
no IOL-Device available
1
IOL-Device detected and is in
PREOPERATE or OPERATE state
0
no error/warning occured
1
error/warning assigned to
IOL-Device or IOL-Master port
occured
0
invalid I/O process data from
IOL-Device
1
valid I/O process data from device
Handbuch PROFINET