8 Konfiguration und Betrieb mit dem
SIEMENS TIA Portal
8.5.2.3 Fehler-PDU für die "Read/Write"-Sequenz
Offset
Parameter
0
Port Error
2
Error Code
3
Additional Code
Tabelle 20: Fehler-PDU
Port-Fehlercode
No error
Reserved
IOL_CALL conflict
Incorrect IOL_CALL
Port blocked
Reserved
Timeout
Invalid port number
Invalid IOL_Index
Invalid IOL_Subindex
No Device
Reserved
RDREC Fault
WRREC Fault
Unexpected Error
Port Function error
Handbuch PROFINET
Version 2.0 03/2022
®
Inhalt
Error Codes detected by the Linking Module
or Client
IO-Link Error codes according AL_Read/
AL_Write services
IO-Link Error codes according AL_Read/
AL_Write services
Definition
No error detected
–
Inconsistent Header information
Inconsistent Header information
(send-/response)
Port temporary not available
–
No correct termination of
IOL_CALL (Resource Busy
detection)
Invalid port Number or port not
supported
Invalid Index
Invalid Subindex
No device
–
Fault during Read record
invocation
Fault during Write record
invocation
Unspecific Error detected
Port function failed
8.5 IO-Link Device-Parametrierung
Coding
0x0000
0x0001 to 0x06FFF
0x7000
0x7001
0x7002
0x7003 to 0x7FFF
0x8000
0x8001
0x8002
0x8003
0x8004
0x8005 to 0x8051
0x8052
0x8053
0x8054
0x8055
Datentyp
Unsigned16
Unsigned8
Unsigned8
Originator
Server
–
Server and/or
Client
Server and/or
Client
Server
–
Client
Client and/or
Server
Client
Client
Client
–
Client
Client
Client
Server
105