Shielding (Functional Erth)
Note that protection from influence by
electromagnetic fields is not provided if
the shield is not earthed.
Connect the shield at each cable end to system
X
ground over a large area.
Avoid pointed contact and twisting of the shield.
X
6.4
Protective Earth Conductor
There is no protective earth conductor.
6.5
Protective earthing
The motor housing must be earthed
to comply with EMC conformity. Cable
shields must be low-inductive earthed
on both sides.
For electrically isolated assembly, the motor housing
X
must be connected to the machine earth via a sepa-
rate earth connection.
Connect and earth the ground of the power and logic
X
supply at a defined location in the system.
Version 13-01-2022