Herunterladen Inhalt Inhalt Diese Seite drucken

Technical Data For; Ex-D Auxiliary Contacts (Aux-S) For Ex-D Switch Block Ghg25; Circuits; Ghg 252 - Eaton CROUSE-HINDS Serie Betriebsanleitung

Explosionsgeschützter schalter
Vorschau ausblenden Andere Handbücher für CROUSE-HINDS Serie:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

1�3

Technical data for:

Ex-d auxiliary contacts (AUX-S) for Ex-d switch block GHG25

EU-Type Examination Certificate:
Marking acc. to 2014/34/EU and standard:
IECEx Certificate of Conformity:
Category of application:
Perm. operating temperature range
Tested ambient temperature range (Ex-d)
Perm. storage temperature in original packing:
Protection category acc. to IEC/EN 60529:
Rated operational voltage U
:
e
Rated insulation voltage U
:
i
Rated impulse withstand voltage
Rated current I
n:
Rated frequence:
Switching capacity I
: (EN 60947-5-1)
e
AC-15A
DC-13
Perm. short circuit back-up fuse:
Version with gold-tipped contacts:
Number of poles:
Terminals: (for cables acc. to EN/IEC 60228):
single-strand clase 1
fine-, multi wire with ferrules, clase 2, 5, 6
fine-, multi wire with double ferrules, clase 2, 5, 6
Test torque
terminals:
Weight:
1�4
Technical data for:
Intrinsically safe circuits
Max. safe voltage U
m
Explosion-protected switch

GHG 252

AC
DC
U
e
U
e
BVS 19 ATEX E 024 U
II 2 G Ex db eb IIC Gb
IECEx BVS 19. 0025 U
Ex db eb IIC Gb
-55 °C ... +103 °C
-55 °C ... +90 °C
-55 °C ... +90 °C
IP2x
≤ 500 V
≤ 250 V
≤ 690 V
6 KV
≤ 6 A
50 ... 60 Hz
220 - 240 V
400 - 415 V
500 V
6 A
6 A
2,5 A
60 V
125 V
4 A
1.2 A
10 A gG at 415 V / 50 Hz
max. 400 mA
2 pole; 1NO, 1NC
1 x 0,5
... 2,5 mm²
1 x 0,5
... 2,5 mm²
2 x 0,5
... 1,5 mm²
0,6 Nm
approx. 53 g
up to 90 V, 50/60 Hz
Safe galvanic isolation from all other circuits
and earth.
GB
17

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Crouse-hinds ghg252

Inhaltsverzeichnis