Herunterladen Inhalt Inhalt Diese Seite drucken

Technical Data Table; Ups Technical Data Table - Riello 5000VA Installations- Und Bedienungsanleitung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 68
UPS

TECHNICAL DATA TABLE

MODELS
INPUT (1 Ø + N star configuration voltages)
Nominal voltage
Acceptable range
Voltage range for which no battery intervention
Nominal frequency
Maximum current (1)
Nominal current (2)
Power factor
Current distortion @ maximum load
BYPASS (on L1)
Voltage range accepted for switching
Frequency range accepted for switching
Switching time
BATTERY
Recharge time (8)
OUTPUT
Nominal voltage
Static variation (3)
Dynamic variation (4)
Waveform
Voltage distortion @ linear load
Voltage distortion @ distorting load
Frequency (5)
Current peak factor
Nominal power in VA
Nominal power in W
Short circuit current
VARIOUS
Leakage current (to ground)
AC/AC yield
Ambient temperature (6)
Relative humidity
Protections
Hold-up time
Noise level
Dimension H x L x D (mm)
Weight in Kg (estimate)
All manuals and user guides at all-guides.com
5000VA
from 184 to 138Vac between 100% and 50% of load in linear mode
30A
24A
5000
4000
Excessive battery discharge – overcurrent – short-circuit – overvoltage –
89 Kg
T
ECHNICAL DATA TABLE
220 – 230 – 240 Vac single-phase
0 - 280 Vac
Maximum voltage 276Vac
Minimum voltage:
Return to mains operation at 190Vac
50 - 60 Hz ±5 Hz
≥ 0.95
≤ 6%
180 - 264 Vac
Frequency selected ±5%
0.1ms
6-8 h
220 / 230 / 240 Vac selectable ±1.5%
1.5% (7)
≤ 5% in 20 ms
Sinusoidal
≤ 3%
≤ 6%
50 or 60 Hz selectable
≥ 3 : 1
1.5 x In per t=0.5sec
≤ 10mA
92 %
0 – 40 °C
< 90 % non-condensing
undervoltage –thermal
≥ 40msec
< 45 dB(A) at 1 m
615mm x 282mm x 785mm
6000VA
36A
28,5A
6000
4800
90 Kg
63

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

6000va6500va8000va10000va

Inhaltsverzeichnis