Herunterladen Inhalt Inhalt Diese Seite drucken

Advanced Settings - Riello 5000VA Installations- Und Bedienungsanleitung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 68
U
SE
FUNCTION
DESCRIPTION
Alarm threshold
Selects the user
for maximum
overload limit
load
Selects the level of
Display
brightness of the LCD
brightness
Selects the operating
Acoustic alarm
mode of the acoustic
Selects the operating
Auxiliary socket
mode of the auxiliary
(power share)
Selects the allowed
input frequency range
for the passage onto
Input frequency
tolerance
bypass and for
synchronization of the
Selects the allowed
Bypass voltage
voltage range for the
thresholds
passage onto bypass
Selects the allowed
Bypass voltage
voltage range for
thresholds for
operation in ECO
ECO
Selects the sensitivity
Sensitivity of
of intervention during
intervention for
operation in ECO
ECO
Power supply of the
Power supply of
load on bypass with
the load in stand-
UPS switched off
by
(stand-by state)
Selects the mode of
Bypass operation
use of the bypass line
56
All manuals and user guides at all-guides.com
PREDEFINED
Disabled
Maximum
display
Low
alarm
Always
connected
socket

ADVANCED SETTINGS

± 5%
output
Low:
180V
High: 264V
Low:
200V
High: 253V
mode
Normal
mode
Disabled (load
NOT powered)
Enabled /
High sensitivity
POSSIBLE CONFIGURATIONS
• Disabled
• 0 ÷ 103 in 1% steps
Minimum ÷ Maximum in 20 steps
• Normal
• Low: does not sound for momentary
bypass intervention
• Always connected
• Disconnection after n seconds of
operation from battery
• Disconnection after n seconds from
the end of discharge prealarm signal
• ... (see UPSTools manual)
• ± 0.25%
• ± 0.5%
• ± 0.75%
• ± 1÷ ±10 in 1% steps
Low: 180 ÷ 200 in 1V steps
High: 250 ÷ 264 in 1V steps
Low: 180 ÷ 220 in 1V steps
High: 240 ÷ 264 in 1V steps
• Low
• Normal
• High
• Disabled (not powered)
• Enabled (powered)
• Enabled/High sensitivity
• Enabled/Low sensitivity
• Disabled with input/output
synchronization
• Disabled without input/output
synchronization
MODE

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

6000va6500va8000va10000va

Inhaltsverzeichnis