6.4 Conditions for the electrical
connection
Specifications for the sub-distribution:
Each charging point must have its own supply line
k
with appropriate fuse protection.
The wallbox needs a suitable line circuit breaker
k
and residual current circuit breaker.
Since the wallbox already has a DC fault detection
k
>6mA, you do not need a RCD type B.
If possible, use overvoltage protection in the sub-
k
distribution.
Observe the labeling of the connection terminals
k
(L3, L2, L1, N, PE).
Use the cable cross-sections specified in the table.
k
Terminals used:
Manufacturer:
Make:
Product Family:
Type:
Rated data
Rated cross section:
Rated voltage:
Rated impulse withstand voltage:
Rated current:
Power dissipation:
Standards:
Current at max. conductor:
Clampable conductors (rated connection)
Conductor cross-section AWG
Conductor cross-section, solid
Conductor cross-section, flexible with end sleeves
with plastic collar DIN 46228/4
Material
Color
Flammability class according to UL94
Continuous service temperature
5 SAFETY RULES:
Before starting to work:
• Disconnect
• Secure against restarting
• Check that no voltage is present
• Ground and short-circuit
• Cover or short-circuit
surrounding parts that are under
voltage or fence off
NOTE
The charging station does not have its own
mains switch. The circuit breaker of the supply
line serves as the mains disconnection device.
Weidmüller Interface GmbH & Co KG
Klippon®Connect
A-Series
A4C 2.5
2,5 mm²
800 V
8 kV
24 A
0,77 W
IEC 60947-7-1
24 A
min. AWG 12 / max. AWG 28
min. 0,5mm² / max. 2,5 mm²
min. 0,5mm² / max. 2,5 mm²
Wemid
dark beige
V-0
min. -60°C / max. 130°C
DE
EN
33