Herunterladen Inhalt Inhalt Diese Seite drucken

Makita DVP181 Bedienungsanleitung Seite 121

Akku-vakuumpumpe
Vorschau ausblenden Andere Handbücher für DVP181:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 21
AS0VP085MK
Vacuum pump valve w ith gauge
mm diameter
vacuum gauge
( to .1 MPa)
Pointer
5/1
flare female
(UNF1/ -
)
Ball valve
Vacuum pump valve with gauge
Vacuum pump
(1) As shown in the figure above, connect the vacuum
pump valve with gauge to the vacuum pump.
Note: When evacuating refrigeration and air
conditioning equipment that uses R1 , R
any other old refrigerant, attach a 5/1
female x 5/1
diameters to the intake of the pump.
Note: When continuing with the charging of the
chlorofluorohydrocarbon (freon) gas after the
evacuation operation, this job is made easier
by changing the charging hose (yellow) to the
AS VP 85MK hose for vacuum pumps.
( ) Proceed with the evacuation by following the directions
in the Instruction Manual of the vacuum pump.
( ) When the degree of vacuum indicated in the manual
of the refrigeration and air conditioning equipment
manufacturer has been reached, close the ball valve.
Instruction Manual
5/1
flare male
(UNF1/ -
Low side
valve
Charging hose (yellow)
Intake shut-off valve
flare male adapter with different
Please be sure to read this before using
the product.
The vacuum gauge will be broken if a
positive pressure is applied to it.
As such, when the evacuation work is
completed, disconnect the hose which is
connected to the positive pressure side.
The vacuum gauge may malfunction or fail
if it is dropped or subjected to vibration.
If this gauge has been dropped or knocked
into something, immediately inspect it for
damage, cracks and deformation.
)
Manifold
High side
valve
Service
port
Charging hose
(blue)
( ) Leave the units standing for at least 5 minutes, and
check that the pointer of the vacuum gauge does not
swing back.
(5) If the pointer should swing back, it means that there is
or
flare
a leak somewhere so inspect the piping joins and other
such areas, make repairs, and resume the evacuation.
( ) Upon completion of the work, disconnect the hose which
is connected to the vacuum pump valve with gauge.
A n j o , A i c h
W arning
Low pressure side
Outdoor unit
M a k i t a C o r p o r a t i o n
3 - 11- 8 , S u m i y o
i 4 4 6 - 8 5 0 2 J a
w w w . m a k i t a . c o m
DVP181-ENAU-LEAFLET-
s h
i - c h
o ,
p a n
1

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis