2.2.2

Procedure for Setting Data (LCD Keypad)

1. Press MODE key until the desired parameter group is displayed.
2. Press ▲ or ▼ keys to move to the desired parameter code. If you know the desired parameter code, you
can set the code number of each parameter group in "Jump code", except DRV group.
3. Press PROG key to go into the programming mode, the cursor starts blinking.
4. Press SHIFT/ESC key to move the cursor to the desired digit.
5. Press ▲ or ▼ keys to change the data.
6. Press ENT key to enter the data. The cursor stops blinking.
Note: Data cannot be changed when:
1) The parameter is not adjustable during the inverter is running. (Refer to the function table in Chapter 5),
or,
2) Parameter Lock function is activated in FU2-94 [Parameter Lock].